Ut:
Measurement test voltage [V].
f:
Measurement frequency [Hz].
Itx:
Measurement current [A] through test object (depending on measurement mode). This is the total
current through the test object.
If you tap on it, it will change to Ir, Ic, Ix
10k
.
Ir: Resistive current (in phase with an ideal resistor)
Ic: Capacitive current (in phase with an ideal capacitor)
Ix
10k
: Calculated total current you would have, when you have 10kV over this test object.
P:
Power [W] over test object.
If you tap on it, it will change to P
10k
: Then it shows the Power [W] @ 10kV. This is the calculated
power you would have, when you have 10kV over this test object.
ϑm:
If you connect a temperature probe (TP01), you will see the measured temperature.
If the receptacle “Temp” is open, you can click on ϑm: and enter the temperature manually.
Single / Multi
1
Single: Starts a single measurement.
Multi: Starts measurements with multiple parameters
Cont
Starts a continuous measurement.
Print
Prints the measured result.
Save
Saves the measured results.
New
Opens the menu for a new transformer template or a new measurement.
1 It depends on the selected Test Mode or voltage- / frequency sweep