EasyManuals Logo

RBI Boiler User Manual

RBI Boiler
154 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #113 background imageLoading...
Page #113 background image
113
A = Left ignition electrode
B = Right ignition electrode
C = Flame detection electrode
Figure 15-8 Positioning electrodes on burner
(Use a hand caliper to verify the distances)
B
A
020010.01.018
Figure 15-9 Remove the air lter “B”
15.4 - Correct
positioning of
the ignition and
ame detection
electrodes
For the heater to work properly the
electrodes must be positioned as
shown in Figure 15-8:
the distance between the ignition
electrodes “A” and “B”, must be
between 0.08 in (2 mm), and 0.10
in (2.5 mm);
the distance of the ignition
electrodes to the burner surface
must be between 0.20 in (5.0 mm),
and 0.22 in (5.5 mm);
the distance of the ame detection
electrode to the burner surface
must be between 0.23 in (6.0 mm),
and 0.27 in (7.0 mm).
NOTICE! To insure correct functioning
of heater the distances listed above
shall be veri ed very carefully also
using a hand caliper.
15.5 - Clean the air
lter
For the heater to work properly the air
lte must be clean. A dirty air lter can
cause a power input reduction of the
unit, resulting in system malfunctions.
Operate as follow in order to clean the
air lter:
1. follow the steps in Section 15.2
to gain access to the internal
components;
2. pull down with a rotation the air
lter “B” as per Figure 15-9
3. pull back the air lter and remove it
from the unit.
4. with compressed air, clean the
surface of the air lter;
5. reassemble the air lter
15 - MAINTENANCE

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RBI Boiler and is the answer not in the manual?

RBI Boiler Specifications

General IconGeneral
BrandRBI
ModelBoiler
CategoryBoiler
LanguageEnglish

Related product manuals