Vacuum spray degassing — 06.07.2016 - Rev. B English —
Time setting for Continuous degassing.
For commissioning, we recommend to set the time for continuous degassing
depending on the system volume and the glycol content, see chapter
5.3 "Operation"
on page 14 .
Time Continuous. degas.
-up" sub-menu. Make-up
Switch to the next list item.
Make-up
-up cycle. Upon expiry of the set time, the system interrupts the
-up and returns the "Make-up time" fault message.
Max. make-up time
If the set number of make
-up cycles is exceeded within 2 hours, the system interrupts the
-up and returns the "Make-up cycles" fault message.
Max. make-up cycles
This setting is relevant for the actuation of the "CD" 3
-ways motor ball valve in make-up
-up pressure > system pressure
-up pressure ≤ system pressure
Make-up pressure
FQIRA+ contact water meter is installed, see chapter 4.6 "Optional equipment and
accessories" on page 13 .
This is the prerequisite for the make-up quantity monitoring and the operation of a
softening system.
With water meter
A contact water meter is not installed (standard).
Only displayed if "YES" has been set in the "With water meter" menu option.
Make-up quantity
Delete meter:
The displayed make-up quantity is set to 0.
The displayed water quantity is retained.
Only displayed if "YES" has
been set in the "With water meter" menu option.
When the set quantity is exceeded, the system interrupts the make
-up process and returns
the error message "Max. make
-up quantity exceeded".
Max. make-up quantity
Only displayed if "YES" has been
set in the "With water meter" menu option.
With softening
The system offers more queries regarding the softening process.
The system does not offer more queries regarding the softening process.
Only displayed if "YES" has been
set in the "With softening" menu option.
Lock make-up?
The system stops the make-up process when the set soft water capacity is exceeded.
The system does not stop the make-up process. The system displays the "Softening"
message.