44 REFUsol 40K / 46K-MV REFU Elektronik GmbH
• Power-up time
• K factor (fault ride through)
REFUset
can be downloaded from www.refu.com.
Pos: 63 /Inverter M anuals/Konf iguration/Ko mmunikation üb er Ethernet/ Einleitung/W R @ 1\mo d_140507633590 5_641.docx @ 7132 @ 2 @ 1
6.5
Communication via Ethernet
The settings for the Ethernet communication can take place either manually or automatically (via DHCP).
Manually is the default setting.
Pos: 64 /Inverter M anuals/Konf iguration/Ko mmunikation üb er Ethernet/ Automatisc he Einstellun g über DHCP/WR @ 1\mod _1405076399 568_641.docx @ 7138 @ 3 @ 1
6.5.1
Automatic Setting via DHCP
1. Navigate to Menu
Configuration > Communication > Ethernet > DHCP
.
2. Enter “1” in DHCP input field.
3. Press
OK
to confirm.
4. Restart inverter by opening and re-closing the DC switch.
The settings for IP address, subnet mask, standard gateway and DNS are automatically taken from
the DHCP server, e.g. the router.
Pos: 65 /Inverter M anuals/Konf iguration/Ko mmunikation üb er Ethernet/ Manuelle Einst ellung/W R @ 1\mod_1 40507646644 2_641.docx @ 71 44 @ 3 @ 1
6.5.2
Manual Setting
In order to ensure a trouble-free operation, all values must be given by the responsible network
administrator and individually set in each inverter.
1. Navigate to
Configuration > Communication > Ethernet > IP address
.
2. Enter IPv4 address. The IPv4 address is arbitrary, but must be consistent throughout the subnet.
Default value:
192.168.130.30
3. Press
OK
to confirm.
4. Navigate to
Configuration > Communication > Ethernet > Subnet mask
.
5. Enter IPv4 mask. The IPv4 mask is arbitrary, but must be consistent throughout the subnet Default
value:
255.255.0.0
6. Press
OK
to confirm.
7. Navigate to
Configuration > Communication > Ethernet > Standard gateway
.
8. Enter the address of the router that allows connection to the internet
Default value:
192.168.1.1
9. Press
OK
to confirm.
10. Navigate to
Configuration > Communication > Ethernet > DNS
.
11. Enter arbitrary IPv4 address of the superior DNS server
Default value:
0.0.0.0
12. Press
OK
to confirm.
13. Restart inverter.