EasyManuals Logo

Regin RCF Series User Manual

Regin RCF Series
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
RCF manual Chapter 14 Display handling 39
Number of
parameter
Description
Factory
setting (FS)
65 Setting, active buttons
RCF:
0 = No active buttons
1 = Only On/Off button active
2 = Only Up/Down buttons active
3 = On/Off and Up/Down buttons active
4 = Only fan button active
5 = On/Off and fan button active
6 = Up/Down and fan button active
7 = All buttons active
RCFM:
0 = No active buttons
1 = Only On/Off button active
2 = Only Up/Down buttons active
3 = On/Off and Up/Down buttons active
4 = Only M button active
5 = Fan and M buttons active
6 = Up/Down and M buttons active
7 = All buttons active
7
66 Function to prevent users from manually setting the fan speed if the fan
should not run due to cooling/heating output, as specified in parameter
25.
0 = Not active
1 = Active
0
67 The EC fan will start when the output exceeds the set value.
(only RCF-230CTD-EC)
10
68 The maximum speed of the EC fan (only RCF-230CTD-EC) 100
69 Fan kickstart. The fan will run 100 % when starting up for the set time,
0...10 seconds.
0
70 Supply air max limitation for cascade control and heating control 35°C
71
Supply air min limitation for cascade control and heating control
24°C
72
Supply air max limitation for cascade control and cooling control
24°C
73
Supply air min limitation for cascade control and cooling control
12°C
74 Cascade factor between room controller and supply air controller 3°C
75
Frost protection temperature for supply air when supply air temperature
limitation is active
8°C
76 Activate supply air temperature limitation for:
0 = Heating control
1 = Cooling control
2 = Both heating and cooling control
1
*NO = Normally Open, NC = Normally Closed

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Regin RCF Series and is the answer not in the manual?

Regin RCF Series Specifications

General IconGeneral
BrandRegin
ModelRCF Series
CategoryController
LanguageEnglish

Related product manuals