The DHW heating function can be used to heat the DHW
store by demanding an afterheating.
The allocated demand relay of the heating circuit is
switched on when the temperature at the allocated sensor
Sen. DHW falls below the adjusted switch-on temperature
TDHW. When the temperature at the allocated sensor ex-
ceeds the adjusted switch-off temperature TDHW off, the
relay is switched off.
When the Timer option is activated, a weekly timer ap-
pears. With this timer, time frames for the functions can be
adjusted.
When the Loading pump option is activated, the loading
pump is switched on in parallel to the DHW afterheating
demand.
The Legionella protection option can be used to contain
the spread of Legionella in DHW stores by systematically
activating the afterheating.
When the Legio prot. option is activated, the controller
heats up the DHW store such that the temperature at
Sen. DHW exceeds a temperature of 60 °C for 30 minutes
every day at 7:00 p.m.
DHW heating option
(available only when the heating circuit afterheating has
been activated)
Arrangement/Heat. circuit/HC/Expert/DHW heat.
Selection: „Yes“, „No”
Factory setting: „No”
DHW priority option
(available only when the DHW heating option has been
activated)
Arrangement/Heat. circuit/HC/Expert/DHW priority
Selection: „Yes“, „No”
Factory setting: „No”
Arrangement/TDHW/TDHW on
Adjustment range: 0,0 ... 94,0 °C
Factory setting: 50,0 °C
Arrangement/TDHW/TDHW off
Adjustment range: 1,0 ... 95,0 °C
Factory setting: 55,0 °C
Arrangement/TDHW/Timer
Selection: „Yes“, „No”
Factory setting: „No”
Arrangement/TDHW/Timer/t1(...21)-on
Adjustment range: 00: 00 ... 00:00
Factory setting: Mo., 06:00 (t1-on), Mo., 17:00 (t2-on)...
Arrangement/TDHW/Timer/t1(...21)-off
Adjustment range: 00: 00 ... 00:00
Factory setting: Mo., 09:00 (t1-off), Mo., 22:00 (t2-off)...
Loading pump option
(available only if relay 3 DeltaSol
®
E is free)
Arrangement/Heat. circuit/HC/Expert/Load p.
Selection: „Yes“, „No”
Factory setting: „No”
Arrangement/Heat. circuit/HC/Expert/Sen. DHW
Selection: 1 … 10
Factory setting: 3
Legionella protection option
Arrangement/Heat. circuit/HC/Expert/Legio prot.
Selection: „Yes“, „No”
Factory setting: „No”

Other manuals for Resol DeltaSol E

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Resol DeltaSol E and is the answer not in the manual?

Resol DeltaSol E Specifications

General IconGeneral
BrandResol
ModelDeltaSol E
CategoryController
LanguageEnglish

Related product manuals