Installation Indications, functions and options MessagesCommissioningOperation and function
ST1(2)
Maximum store temperature
monitoring store 1, 2
Selection: ON / OFF
Factory setting: ON
ST1(2)MX
Maximum store temperature
exceedance counter
STMAX
Maximum store temperature
monitoring option
Selection: ON / OFF
Factory setting: OFF
STMAX
PUSH
Maximum store temperature
This function is used for detecting and indicating if the adjusted maximum store
temperature has been exceeded. The controller compares the current store tem-
perature to the adjusted maximum store temperature, thus monitoring the store
loading circuits.
The maximum store temperature is considered exceeded when the temperature
measured at the store sensor exceeds the adjusted maximum store temperature by
at least 5 K. The monitoring becomes active again as soon as the store temperature
falls below the adjusted maximum store temperature.
The channels ST1, ST2 can be used for selecting the stores to be monitored. The
number of exceedances is displayed in the ST(2)MX channels. A possible cause for
an unwanted exceedance of the maximum store temperature is a defective valve.
Note
Only if the installer code is entered (see page 51), will the option be avai-
labe.
OFF ON
OK
a b c
BACK
PUSH
BACK
PUSH
24
CODE
The user code can be entered in the CODE menu (see page 51).
25
Reset
By means of the reset function, all adjustments can be set back to the factory set-
tings. To do so, the installer code must be entered (see page 51).
24
RESET 25
PUSH
CODE 24
PUSH
25
23

Table of Contents