Recommendation for complex systems: Install drive components in one cabi‐
net and the control units in a second, separate cabinet.
Badly grounded control cabinet doors act as antennas. Therefore, connect
the control cabinet doors to the cabinet on top, in the middle and on the bot‐
tom via short equipment grounding conductors with a cross section of at least
6 mm
2
or, even better, via grounding straps with the same cross section.
Make sure connection points have good contact.