SECTION II: INSTALLATION AND MAINTENANCE
35
II.12 CHECK-LIST
PROBLEM RECOMMENDED ACTION
1 - OUTLET PRESSURE HIGH
Insufficient cooling air at air-side exchanger: check clearances and make sure coils are not obstructed.
Fan does not run check fan operation.
Excessive refrigerant charge. drain the excess.
2 - OUTLET PRESSURE LOW
1 - identify and eliminate any leaks;
Insufficient refrigerant charge.
2 - restore correct charge.
Mechanical problems in the compressor: replace compressor
3 - INLET PRESSURE HIGH
Excessive thermal load: check system sizing, infiltrations and insulation.
Irregular operation of the expansion valve: check operation.
Mechanical problems in the compressor: replace compressor
4 - INLET PRESSURE LOW
1 - identify and eliminate any leaks;
Insufficient refrigerant charge.
2 - restore correct charge.
Filter partially obstructed (appears frosted): replace filter.
Irregular operation of the expansion valve: check operation.
Presence of air in the water system: bleed the water system.
Insufficient water flow: check circulation pump operation.
5 - THE COMPRESSOR DOES NOT START
Microprocessor board alarm: identify alarm and take appropriate action.
No voltage, switch open: close the switch.
1-reset the switch / electronic control;
Overload protection triggered:
2-check the unit at start up.
No request for cooling with user system set point correct: check and if necessary wait for cooling request.
Working set point too high: check and if necessary readjust set-point.
Defective contactors: replace contactor.
Compressor electric motor failure: check for short circuit.
6 - THE COMPRESSOR MAKES A BUZZING NOISE
Incorrect power supply voltage: check voltage, investigate causes.
Compressor contactor stuck: replace contactor.
Mechanical problems in the compressor: replace compressor
7 - THE COMPRESSOR STARTS AND STOPS
Faulty low pressure switch: check pressure switch calibration and operation.
1 - identify and eliminate any leaks;
Insufficient refrigerant charge.
2 - restore correct charge.
Refrigerant line filter clogged (appears frosted). replace filter.
Irregular working of the expansion valve: check operation.
8 - THE COMPRESSOR STOPS
Faulty high pressure switch: check pressure switch calibration and operation.
1 - check clearances and make sure coils are not obstructed.
Insufficient cooling air at air-side exchanger:
2 - check fan operation.
Excessive ambient temperature: check unit operation limits.
Excessive refrigerant charge. discharge surplus refrigerant.
9 - THE COMPRESSOR IS NOISY AND VIBRATES
1 - check expansion valve operation.
2 - check superheating.
Compressor is pumping liquid, excessive refrigerant fluid in crankcase.
3 - adjust superheating, if necessary replace expansion valve.
Mechanical problems in the compressor: replace compressor
Unit running at the limit of specified conditions of use. check unit operation limits.
10 - THE COMPRESSOR RUNS CONTINUOUSLY
Excessive thermal load: check system sizing, leakage and insulation.
Working set point too low in cooling cycle (too high in heating cycle). check setting and reset.
1 - identify and eliminate any leaks;
Insufficient refrigerant charge.
2 - restore correct charge.
Refrigerant line filter clogged (appears frosted). replace filter.
Control board faulty: replace the board.
Irregular working of the expansion valve: check operation.
Compressor contactor stuck: replace contactor.
1 - check clearances and make sure coils are not obstructed.
Poor ventilation to the coil:
2 - check fan operation.
11 - THE FAN DOES NOT WORK OR STARTS AND STOPS
1 - check for short-circuits
Thermal protection activated:
2 - replace motor.
12 - THE CIRCULATION PUMP DOES NOT START
Lack of voltage to the pump unit: check electrical connections.
Absence of signal from the control board: check.
Pump blocked: unblock the pump.
Pump motor failure: replace the pump.
Remote ON/OFF switch in OFF position): put in ON position.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RHOSS MICROSYSTEM TCCE 114 Series and is the answer not in the manual?

RHOSS MICROSYSTEM TCCE 114 Series Specifications

General IconGeneral
BrandRHOSS
ModelMICROSYSTEM TCCE 114 Series
CategoryChiller
LanguageEnglish

Related product manuals