Calibration and operation
6.8 Parameter modes of operation
The parameters memorised in the LME7... burner control can be
displayed and modified in the Parameters level.
6.8.1 Parameters without index, with direct display
Example of parameter 225 (pre-purging time) on the Param-
eters level
Press for the pre-purging time.
Display: Parameter 225: blinks, the value 3.675 does not blink.
Press “i/reset” for the modification mode.
Display: 3.675.
Press or to move the previous pre-purging time
by the
mode
one place to the left.
Display: the pre-purging time 3.675 blinks.
Note:
To detect display errors, the value appears shifted by one posi-
tion to the left.
Press or for the required pre-purging time.
Display: The pre-purging time 3.822 blinks.
Alternative 1:
Fig. 125
Delete the change!