380-400-415 V AC Three-phase with neutral (4 wire)
Maximum input current
(1)
Input voltage tolerance accepted for
no battery intervention (referred to
400V AC)
20% @ 100% load
-40% +20% @50% load
Input frequency tolerance accepted
for no battery intervention (referred
to 50/60Hz)
Input current Harmonic Distortion
Programmable from 1 to 125 sec. at steps of 1 sec
380/400/415 V AC three-phase with neutral (4 wire)
Nominal apparent power in output
Nominal active power in output
Output voltage precision (referred to
output voltage 400V AC)
Output voltage harmonic distortion
with linear load and normalized
distortion
1% with linear load
3% with distorted
load
1% with linear load
3% with distorted
load
1% with linear load
3,5% with distorted
load
Crest factor accepted at nominal
load
Frequency accuracy in free running
mode
Inverter overload (Vin>345V AC )
103% Infinite, 110% 10 min, 125% 1 min
110% Infinite,125% 60 minutes, 150% 10 minutes
Maximum recharging current