EasyManuals Logo

Rinnai I Series Installation Manual

Rinnai I Series
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
Rinnai 11 I Series Evap AC IM
4.1 EVAPORATOR MODULE
The Evaporator Module is where heat transfer through evaporation takes place and this shall be installed within
the roof space� The Evaporator Module contains the Rinnai I Series control system and water distribution system
which supplies water to the cooling pads� This shall be installed on the Safety Tray supplied by Rinnai�
4.2 VENTILATION – FRESH AIR INTAKE
It is the installer’s responsibility to ensure the minimum air intake requirements are met to service the Rinnai I
series Evaporator Module�
The minimum air intake requirement for the I20 model is 0�5 m² open area and for the I10 model is 0�3 m² open
area� This may be achieved with the use of an Roof Cap, Rinnai I Series Eave Vents, roof vents, or gable vents�
The Roof Cap and Rinnai I Series Eave Vents are air intake accessories available from the Rinnai for BAL and non-
BAL installations� The I20 model requires eight (8) Rinnai I Series Eave Vents and the I10 model requires four (4)�
4.3 FIX AND SEAL THE ROOF FLASHING
If you install an Roof Cap refer to the installation instructions
supplied with the Roof Cap and the following guidelines�
The Colorbond™ roof ashing (installer supplied) shall be xed
and sealed to the dropper duct to prevent water entry into the
building�
Installations where the Cooler is more than 4 metres downstream
from the roof peak should be tted with an additional water
diverting channel on the dropper duct high side, that extends
beyond the dropper duct sides by at least 50mm (see diagram
right)�
4.4 RINNAI I SERIES EAVE VENT INSTALLATION
Rinnai I Series Eave Vents shall be installed with six fasteners each (installer supplied), which are suitable with the
type of material the eave vents are being secured to�
There should be a minimum distance of 20mm from the outer edge of eave vent to edge of eave material and
between eave vents�
Using dimensions A & B of the eave vent inner border (diagram below), mark out the eave vent location, remove
eave material and secure the eave vent�
NOTE
Eave vents should be installed between joists where practicable.
Flashing
Water diverter channel
Dropper Duct
Rain water
Eave edge
A
Min
20mm
Min
20mm
B
Min 20mm
4. COOLER HARDWARE

Table of Contents

Other manuals for Rinnai I Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rinnai I Series and is the answer not in the manual?

Rinnai I Series Specifications

General IconGeneral
BrandRinnai
ModelI Series
CategoryBoiler
LanguageEnglish

Related product manuals