Rishabh RISH Master 3440 - 9.1 User Assignable Modbus Registers:

Default Icon
97 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Address Parameter Description
40089
to
40105
to
40117
Energy
Start
Count
40107
The user can set respective energy starting count in these
registers (before the user can write values to these locations
user needs to check register 40005 i.e Energy on RS485 and
register 40036 i.e Energy digit reset count). Valid range is
0-9999999. For E.g if Energy on RS485 is in K and Energy
digit reset count is 7 the start count should be in k and
value should be less than 7 digits.
to
40129
Energy
40119
The user can set respective Energy Overow starting count
in these registers. Valid range is 0-999999.
Overflow
Start
Count
-
-