2. SETTING
IMCB04-E10
9
(3) SL3 (Heater break alarm [HBA], control loop break alarm [LBA], special
specification, or control loop break alarm [LBA] output selection )
Cannot be used the heater break alarm (HBA) for the following instruments.
Instrument without the alarm 2 (ALM2) output.
Instrument of the process alarm, deviation alarm, band alarm, SV alarm or control
loop break alarm (LBA) is used as the alarm 2 (ALM2).
Instrument whose control output is the current output type.
Cannot be used the control loop break alarm (LBA) for the following instruments.
Instrument without both the alarm 1 (ALM1) output and the alarm 2 (ALM2) output.
Instrument whose control action is the A type or W type.
Cannot be output the control loop break alarm (LBA) from the alarm 1 (ALM1) for the
following instruments.
Instrument without the alarm 1 (ALM1) output.
Instrument of the process alarm, deviation alarm, band alarm or SV alarm is used
as the alarm 1 (ALM1).
Cannot be output the control loop break alarm (LBA) from the alarm 2 (ALM2) for the
following instruments.
Instrument without the alarm 2 (ALM2) output.
Instrument of the process alarm, deviation alarm, band alarm, SV alarm or heater
break alarm (HBA) is used as the alarm 2 (ALM2).
Instrument with the Z-168 specification.
Factory set value varies depending on the instrument specification.
Set value Description
0 Heater break alarm (HBA) not provided
1 Heater break alarm (HBA) provided
1
Heater break alarm (HBA)
selection
0 Control loop break alarm (LBA) not provided
1 Control loop break alarm (LBA) provided
Control loop break alarm (LBA)
selection
0 Z-132 specification not provided
2
1 Z-132 specification provided
3
Special specification selection
0 LBA is output from alarm 1
1 LBA is output from alarm 2
Selection of control loop break
alarm (LBA) output terminals
1
When be shipped with “heater break alarm (HBA) provided,” “Z-132 specification provided” is set.
2
Normal HBA action.
3
If heater break or welding continues for more than three seconds, a heater break alarm (HBA) will
occur.

Other manuals for RKC INSTRUMENT CB100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RKC INSTRUMENT CB100 and is the answer not in the manual?

RKC INSTRUMENT CB100 Specifications

General IconGeneral
BrandRKC INSTRUMENT
ModelCB100
CategoryController
LanguageEnglish

Related product manuals