EasyManua.ls Logo

Robur Next-R - Page 34

Robur Next-R
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Heating engineer
34
3
must be mounted with a downward slope of 2 to 3
cm each 1-m length (Figure 3.7
p.34
), to prevent
condensate drops entering the unit.
If vertical ue gas exhaust pipes longer than 1,5 m
are installed, at the base of the vertically mounted
ue gas exhaust pipe a T-shaped piece must be
tted to collect the condensate, to prevent any
condensate drops from entering the gas unit
heater (Figure 3.2
p.30
).
For each 45° elbow an increment of 1,2 m in length
should be added.
Figure3.7 Slope of horizontal pipes
For proper installation of the wall external terminals for
the ue gas exhaust and combustion air intake, follow the
details given in Figure 3.8
p.34
.
Figure3.8 Wall terminal position
IN combustion air intake
OUT ue gas exhaust
A recommended posi-
tion (OK)
B allowed position (OK)
C position NOT allowed
(NO)
IN
OUT
A
IN
OUT
B
IN
OU
T
C
NOOK
3.3.5 Example of calculation
Let's assume to install a R60 in C13 type installation (Figure
3.3
p.31
). The air/fumes system will be realized with Ø
80 separate pipes in the following way:
7 m of Ø 80 ue gas exhaust pipe
1 90° Ø 80 elbow on the ue gas exhaust pipe
6 m of Ø 80 air pipe
It is therefore possible to proceed with the verication, re-
membering that the maximum allowed pressure drop is
100 Pa (see Table 3.11
p.33
).
Ø 80 ue gas exhaust pipe
7 m x 9,2 Pa/m = 64,4 Pa
90° elbow
1 x 15,4 Pa = 15,4 Pa
Ø 80 air pipe
6 m x 4,4 Pa/m = 26,4 Pa
Total pressure drop = 106,2 Pa
Total pressure drop of the piping system is greater than
the maximum allowed pressure drop (100 Pa), therefore
the installation is not allowed.
The installation can be done if one of the following steps
is taken:
Reduce the length of the air/fumes pipes.
Increase pipe diameter, e.g. by using Ø 110. In this case
the total pressure drop would be:
7 m x 1,9 Pa/m = 13,3 Pa
1 x 4,3 Pa = 4,3 Pa
6 m x 0,9 Pa/m = 5,4 Pa
Total pressure drop = 23,0 Pa
which is therefore compatible with the maximum allowed
pressure drop.
3.3.6 Vertical downow gas unit heaters
For vertical downow gas unit heaters, at the base
of the vertically mounted ue gas exhaust pipe a
T-shaped piece must be tted to collect the con-
densate, to prevent any condensate drops from
reaching the blower (Figure 3.9
p.35
).
Pay attention to the collection and the proper con-
veying of the condensate drain.

Related product manuals