EasyManuals Logo

Rockwell Automation 1766-L32BWAA User Manual

Rockwell Automation 1766-L32BWAA
310 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #136 background imageLoading...
Page #136 background image
136 Rockwell Automation Publication 1766-UM001O-EN-P - September 2021
Appendix A Specifications
Figure 64 - 1766-L32BXB, 1766-L32BXBA FET Output
Maximum output current (temperature dependent):
Description General Operation
High Speed Operation
(1)
(Output 2, 3 and 4 Only)
(1) Output 2, 3 and 4 are designed to provide increased functionality over the other FET outputs. Output 2, 3 and 4 may be used like the
other FET transistor outputs, but in addition, within a limited current range, they may be operated at a higher speed. Output 2, 3 and
4 also provide a pulse train output (PTO) or pulse width modulation output (PWM) function.
Power supply voltage 24V DC (-15%, 10%) Class 2
On-state voltage drop:
at max load current
at max surge current
1V DC
2.5V DC
Not Applicable
Not Applicable
Current rating per point
max load
min load
max leakage
See Figure 64
50 mA
1.0 mA
100 mA
50 mA
1.0 mA
Surge current per point:
peak current
max surge duration
max rate of repetition at 30 °C (86 °F)
max rate of repetition at 60 °C (140 °F)
4.0 A
10 ms
once every second
once every 2 seconds
Not Applicable
Not Applicable
Not Applicable
Not Applicable
Turn-On Time, max 11 µs 28 ns
Turn-Off Time, max 89 µs 3.5 µs
0.25
10°C
(50°F)
30°C
(86°F)
50°C
(122°F)
0.75A, 60°C (140°F)
1.5A, 30°C (86°F)
70°C
(158°F)
80°C
(176°F)
0.5
0.75
1.0
1.25
1.5
1.75
2.0
1.0
10°C
(50°F)
30°C
(86°F)
50°C
(122°F)
3.0A , 60°C (140°F)
6.0A , 30°C (86°F)
70°C
(158°F)
80°C
(176°F)
2.0
3.0
4.0
5.0
6.0
7.0
8.0
FET Current per Point FET Total Current
Current (Amps)
Current (Amps)
Temperature
Temperature
Valid
Range
Valid
Range
AC Input Filter Settings
Nominal Filter Setting (ms)
ON Delay (ms) OFF Delay (ms)
Minimum Maximum Minimum Maximum
8 2.3 2.5 11 12
High-Speed DC Input Filter Settings (Inputs 0…11)
Nominal Filter Setting (ms)
ON Delay (ms) OFF Delay (ms)
Maximum Counter Frequency (Hz) 50% Duty Cycle
Minimum Maximum Minimum Maximum
0.005 0.001 0.005 0.001 0.005 100.0 kHz
0.008 0.003 0.008 0.003 0.008 60.0 kHz
0.0125 0.0075 0.0125 0.007 0.0115 40.0 kHz
0.025 0.019 0.025 0.018 0.023 20.0 kHz
0.075 0.062 0.072 0.066 0.074 6.7 kHz
0.100 0.089 0.100 0.088 0.098 5.0 kHz
0.250 0.229 0.250 0.228 0.248 2.0 kHz
0.500 0.459 0.500 0.455 0.492 1.0 kHz
1.00 0.918 0.995 0.910 0.979 0.5 kHz
2.000 1.836 1.986 1.820 1.954 250 Hz

Table of Contents

Other manuals for Rockwell Automation 1766-L32BWAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation 1766-L32BWAA and is the answer not in the manual?

Rockwell Automation 1766-L32BWAA Specifications

General IconGeneral
BrandRockwell Automation
Model1766-L32BWAA
CategoryController
LanguageEnglish

Related product manuals