Rockwell Automation Publication 440G-UM001B-EN-P - May 2016 31
Description of Operation Chapter 4
Status Diagnostic Status Indicators Table B (Series Operation) (continued)
Operation with Control
Systems
Do not use a control system with pulsing or switch off the pulsing function in
your control system. The control system must tolerate these pulses, which may
have a duration of up to 1 ms when the device is configured for series operation
or 300 µs when the device is configured for standalone operation.
X X X X OFF OFF OFF OFF ON 1 x
Error during configuration or invalid
DIP switch setting.
Erron-
eous
X X X OFF OFF OFF OFF ON 2 x
Input error (for example, missing test
pulses, illogical switch state from
previous switch)*
X X X X OFF X X X OFF 3 x
Handle assembly read error (for
example, error in code)**
X X X X OFF OFF OFF OFF ON 4 x
Output error (for example, short
circuit or loss of switching capability)
or short circuit at the outputs*
X X X X OFF OFF OFF OFF ON
Internal fault (for example,
component faulty, data fault)*
X X X X OFF OFF OFF OFF ON 1 x
Signal sequence erroneous (for
example, broken bolt) ***
With active release monitoring:
escape release or manual release was
actuated.*
X X X XXXXXX
Power is ON for a long time with short
interruption
One million operating cycles
exceeded.
X X X X X OFF OFF OFF ON 2 x
Control inputs IMP1, IMP2, IMM
invalid; switch off control inputs for
minimum of half second and switch
on again to reset.
* Latching fault; to reset, use the RST input or briefly disconnect the device from the
power supply.
** Non-latching fault; open safety guard and close it again to reset.
***See Troubleshooting and Assistance in Appendix A on page 59
.
Status indicator
not illuminated
status indicator illuminated
Status indicator
flashes
x
Any state
Position of the Bolt
Tongue
Safety Outputs
FO1A and FO1B
Door Mounting
Output (OD)
Monitoring Output
Bolt Tongue (OT)
Guard Locking Mon-
itoring Output (OL)
Diagnostics Moni-
Access Boxtoring