Rockwell Automation Publication 750-IN119A-EN-P - April 2022 29
Chapter 3 Prepare for Installation
Mounting Surface
Install wall mount products on a flat vertical surface.
Install the product on a clean metal surface that is free of paint and other
coatings.
Install the product in a vertical orientation.
Verify that the product makes full contact with the mounting surface.
Do not use standoffs or spacers.
Environment
The installation site must be compatible with the degree of protection that is
provided by the enclosure.
PowerFlex 755TS products are only intended for indoor use.
Protect the equipment from moisture and direct sunlight.
Do not expose to a corrosive atmosphere.
Protect fans and electronics by avoiding dust or metallic particles.
Temperatures
Enclosure Rating
Operating Temperature
Range without Derating
Maximum Operating
Temperature with Derating
(1)
Frames
Stand-alone/Wall-mount
IP20, NEMA/UL Open Type -20…+50 °C (-4…+122 °F) 60 °C (140 °F) 1…5, All ratings
IP00, NEMA/UL Open Type -20…+50 °C (-4…+122 °F) 60 °C (140 °F) 6 and 7, All ratings
IP20, NEMA/UL Type 1 (with hood) -20…+40 °C (-4…+104 °F) 50 °C (104 °F) 1…5, All ratings
IP20, NEMA/UL Type 1 (with option kit) -20…+40 °C (-4…+104 °F) 50 °C (104 °F) 6 and 7, All ratings
IP54, NEMA/UL Type 12 -20…+40 °C (-4…+104 °F) 50 °C (104 °F) 2…7, All ratings
Flange mount — front
IP20, NEMA/UL Open Type -20…+50 °C (-4…+122 °F) 60 °C (140 °F) 2…5, All ratings
IP00, NEMA/UL Open Type -20…+50 °C (-4…+122 °F) 60 °C (140 °F) 6 and 7, All ratings
Flange mount — back/heatsink
IP66, NEMA/UL Type 4X -20…+40 °C (-4…+104 °F) 50 °C (104 °F)
2…7, All ratings
(2)
(1) See the PowerFlex 755TS Products with TotalFORCE Control Technical Data, publication 750-TD104 for derating guidelines.
(2) Not applicable to 40 Hp/30 kW ND frame 3 drives.
Storage temperature -40…+70 °C (-40…+158 °F)
Relative humidity 5…95% non-condensing
Atmospheric protection
Harsh environment is defined as a copper or silver reactivity level greater than 1000 angstroms
per 30 days exposure.
No condensation allowed.
Maximum allowable humidity is 60% in the presence of corrosive gases.
See ISA-71.04-2013 for details on how to measure reactivity levels on copper and silver test
coupons.