30 Rockwell Automation Publication 750-IN119A-EN-P - April 2022
Chapter 3 Prepare for Installation
Minimum Clearances Specified vertical clearance requirements that are indicated in Figure 11 are
intended to be from the drive to the closest object that can restrict airflow
through the drive heat sink and chassis. The drive must be mounted in a
vertical orientation as shown and must make full contact with the mounting
surface. Do not use standoffs or spacers.
Figure 11 - Minimum Mounting Clearances – Wall Mount Frames 1…7
Airflow through the heat
sink must not be impeded.
76.2 mm (3.0 in.)
76.2 mm (3.0 in.)
Mounting Surface
(See page 29
)
Drives are shown with the optional human
interface module (HIM) installed.
Order this device separately. Choose catalog
number 20-HIM-A6.