70 Rockwell Automation Publication 750-IN119A-EN-P - April 2022
Chapter 5 Power Wiring
Frames 5…7 Common DC
Input Power Terminals
Table 11 - Common DC Input Terminal Designations
Frame Power Terminal Blocks
5
6
(1)
(1) Dynamic Brake Resistor Terminals are optional on Frame 6 and 7 drives: catalog number position 12.
See Catalog Number Explanation on page 11.
7
(1)
Terminal Description Notes
+DC DC bus (+) DC input power
-DC DC bus (–) DC input power
BR1 DC brake (+) Dynamic brake resistor connection (+)
BR2 DC brake (–) Dynamic brake resistor connection (–)
UU (T1)
Motor connections
(1)
(1) IMPORTANT: Motors with NEMA MG1 Part 31.40.4.2 inverter grade insulation systems are recommended. If you
intend to connect a motor that is not rated inverter grade, see Wiring and Grounding Guidelines for Pulse-width
Modulated (PWM) AC Drives, publication DRIVES-IN001 for recommendations.
VV (T2)
WW (T3)
PE /
PE ground
Terminating point to chassis ground for incoming DC line
and motor shield.