28 Rockwell Automation Publication 750-IN119A-EN-P - April 2022
Chapter 3 Prepare for Installation
Location Planning Consider the following when planning the location for your PowerFlex 755TS
product.
• Environment - temperature, humidity, and vibration or shock
• Ventilation and air conditioning
• Input power cable entry points
• Motor cable exit points
• Product dimensions (See page 31
for Approximate Dimensions.)
• Overall height of installation area
• Alignment with other equipment
• Future needs
Table 2 - PowerFlex 755TS 400V/480V Input Drives RF Emission Compliance and
Installation Requirements
Drive Frame
Catalog Number
EN 61800-3 Category C3
(1)
(I ≤ 100 A)
CISPR11 Group 1 Class A
(Input Power > 20 kVA)
(1) Intended to be powered from an industrial power network that is supplied by a dedicated power transformer or generator
and not from LV power lines that supply other customers.
EN 61800-3 Category C3
(1)
I > 100 A
Frame 1
20G…C2P1 thru 20G…C015
20G…D2P1 thru 20G…D014
150m (492.1 ft) motor cable limit with no
filter.
Requires installation of the supplied C3
bracket to ground the motor cable
shield. See page 61
for instructions.
N/A
Frame 2
20G…C2P1 thru 20G…C022
20G…D2P1 thru 20G…D022
150m (492.1 ft) motor cable limit with no
filter.
Requires using the factory installed C3
bracket to ground the motor cable
shield. See page 61
for instructions.
N/A
Frame 3
20G…C030 thru 20G…C061
20G…D027 thru 20G…D053
150m (492.1 ft) motor cable limit with no
filter.
Requires using the factory installed C3
bracket to ground the motor cable
shield. See page 61
for instructions.
N/A
Frame 4
20G…C060 thru 20G…C086
20G…D052 thru 20G…D078
150m (492.1 ft) motor cable limit with no
filter.
Requires using the factory installed C3
bracket to ground the motor cable
shield. See page 61
for instructions.
N/A
Frame 5
20G…C085 thru 20G…C104
20G…D077 thru 20G…D096
150m (492.1 ft) motor cable limit with no
filter.
Requires using the factory installed C3
bracket to ground the motor cable
shield. See page 61
for instructions.
150m (492.1 ft) motor cable limit with no
filter.
Requires using the factory installed C3
bracket to ground the motor cable
shield. See page 61 for instructions.
Frame 6
20G…C104 thru 20G…C260
20G…D125 thru 20G…D248
150m (492.1 ft) motor cable limit with no
filter.
Requires a 20-750-EMC6-F6 EMC C3
option kit or other means of shield
termination within the installation.
(2)
(2) Review the shield termination requirements for EN 61800-5-1 on page 26 and for EN 61800-3 on page 27.
150m (492.1 ft) motor cable limit with no
filter.
Requires a 20-750-EMC6-F6 EMC C3
option kit or other means of shield
termination within the installation.
(2)
Frame 7
20G…C302 thru 20G…C477
20G…D302 thru 20G…D477
N/A
150m (492.1 ft) motor cable limt with no
filter.
Requires a 20-750-EMC6-F7 EMC C3
option kit or other means of shield
termination within the installation.
(2)