Rockwell Automation Publication 750-IN119A-EN-P - April 2022 73
Chapter 5 Power Wiring
75 6 140 20G…C140 154.0 210.0 20G…C170 210.0 255.0 88.9 128.3 175 300 400 — — — 151.4 DCFUSE3S-315A DCFH-NH1
90 6 170 20G…C170 187.0 255.0 20G…C205 255.0 307.5 107.9 155.8 200 300 500 — — — 183.9 DCFUSE3S-315A DCFH-NH1
110 6 205 20G…C205 225.0 307.5 20G…C260 307.5 390.0 130.1 187.8 250 400 600 — — — 221.7 DCFUSE3S-400A DCFH-NH1
132
6
260
20G…C260 286.0 390.0
165.0 238.2 300 500 700 — — — 281.2 DCFUSE5S-500A DCFH-NH2
7
20G…C302 390.0 468.0 165.0 238.2 300 500 700 — — — 281.2 DCFUSE6S-500A DCFH-NH3
160 7 302 20G…C302 332.2 453.0 20G…C367 453.0 550.5 191.7 276.7 350 600 900 — — — 326.7 DCFUSE6S-550A DCFH-NH3
200 7 367
20G…C367 403.5 550.5 20G…C456 550.5 684.0 232.9 336.2 450 700 1100 — — — 397.0 DCFUSE6S-700A DCFH-NH3
20G…C477 550.5 684.0 232.9 336.2 450 700 1100 — — — 397.0 DCFUSE6S-700A DCFH-NH3
250 7 456 20G…C456 501.6 684.0
289.5 417.8 600 800 1300 — — — 493.2 DCFUSE6S-900A DCFH-NH3
270 7 477 20G…C477 524.7 715.5
302.8 437.0 600 800 1300 — — — 516.0 DCFUSE6S-900A DCFH-NH3
(1) Applied rating refers to the motor that is connected to the drive. For example, a C022 drive can be used in Normal Duty mode on an 11 kW motor, or in Heavy Duty mode on a 7.5 kW motor. A C015 drive can be used in Heavy Duty mode on a 5.5 kW motor with
the same ratings as a C011 drive. The drive can be programmed for either mode. For any given drive catalog number, Normal Duty mode provides higher continuous current but smaller overload current when compared to Heavy Duty mode. See parameter
0:36 [Duty Rating Cfg].
(2) Only enclosure codes F, N, and R. See Product Rating Cross-reference on page 14
, for frame sizes of other enclosure types.
(3) This drive is the next larger frame size.
(4) For UL compliance - fast-acting class J (Bussmann DFJ) or fast-acting class T (Bussmann JJS) fuses only. Equivalent fuses of class J, T may be used if they have lower I
peak
and I
2
t ratings than the Bussmann JJS fuse. For CE compliance - type gR fuses
(Bussmann 170M - size 00 to 3, IEC 60269 or DIN 43620, or FWP-_G10F, _G14F, _G22F) only. Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping. Max. source SCCR = 100 kA.
(5) For UL compliance - fast-acting class J (Bussmann DFJ) or fast-acting class T (Bussmann JJS) fuses only. Equivalent fuses of class J, T may be used if they have lower I
peak
and I
2
t ratings than the Bussmann JJS fuse. For CE compliance - type gR fuses
(Bussmann 170M - size 00 to 3, IEC 60269 or DIN 43620, or FWP-_G10F, _G14F, _G22F) only. Maximum protection device size is the highest rated device that supplies drive protection. Max. source SCCR = 100 kA.
(6) Circuit breaker - inverse time breaker - must be used with a fuse specified in the table. For US NEC, minimum circuit breaker size is 125% of motor FLA. Ratings that are shown are maximum values.
(7) Bulletin 140M/140MT with adjustable current range must have the current trip set to the minimum range so that the device does not trip.
(8) Bulletin 140M/140MT is UL Listed for 480Y/277V. Not UL Listed for use on 400V or 480V Delta/Delta, corner ground, or high-resistance ground systems.
(9) Bulletin 140M/140MT must be Frame C (140M-C2E-xxx or 140MT-C3E-xxx) or Frame D (140M-D8E-xxx or 140MT-D9E-xxx). Max. source SCCR = 65 kA.
(10) Bulletin 140M/140MT must be Frame D (140M-D8E-xxx or 140MT-D9E-xxx) or Frame F (140M-F8E-xxx). Max. source SCCR = 65 kA.
(11) When using the Bulletin 140M/140MT, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume that is specified in this column. Application-specific thermal considerations can require a larger enclosure.
(12) DC fuses specified are UL recognized and CE compliant.
400-Volt AC and 540-Volt DC Input Protection Devices—Drive Frames 1…7 (continued)
Applied
Rating
(1)
Frame
(2)
Cont.
Output
Amps
Sized For Normal Duty Sized For Heavy Duty Input Quantities AC Input Protection Devices
Input
Quantities
DC Input Protection
(12)
Cat. No.
Output Overload
Amps
Cat. No.
Output Overload
Amps
Cont. AC Input Fuse
Circuit Breaker
(6)
140M/140MT Type E Combination
Motor Controller with Adjustable
Current Range
(7)
(8)
Cont. DC
Input
Fuse Cat. No.
20-750-…
Fuse Holder
Cat. No.
20-750-…
kW 1 Min 3 s 1 Min 3 s kVA Amps
Min [A]
(4)
Max [A]
(5)
Max [A]
Min. Encl.
Vol. [in.
3
]
Cat. No.
Min Enclosure
Volume [in.
3
]
(11)
Amps
400 Volt AC Input 540 Volt DC Input