Rockwell Automation Publication 750-IN119A-EN-P - April 2022 75
Chapter 5 Power Wiring
150 6 186 20G…D186 204.6 279.0 20G…D248 279.0 372.0 142.9 171.9 225 400 550 — — — 203.0 DCFUSE3S-400A DCFH-NH1
200
6
248
20G…D248 272.8 372.0
190.6 229.2 300 450 700 — — — 270.6 DCFUSE5S-500A DCFH-NH2
7
20G…D302 372.0 453.0 190.6 229.2 300 450 700 — — — 270.6 DCFUSE6S-500A DCFH-NH3
250 7 302 20G…D302 332.2 453.0 20G…D361 453.0 543.6 232.0 279.1 350 600 900 — — — 329.5 DCFUSE6S-550A DCFH-NH3
300 7 361
20G…D361 397.1 541.5 20G…D415 541.5 649.8 277.3 333.6 450 700 1000 — — — 393.9 DCFUSE6S-700A DCFH-NH3
20G…D477 541.5 649.8 277.3 333.6 450 700 1000 — — — 393.9 DCFUSE6S-700A DCFH-NH3
350 7 415 20G…D415 456.5 622.5
318.9 383.6 500 800 1200 — — — 452.8 DCFUSE6S-900A DCFH-NH3
400 7 477 20G…D477 524.7 715.5
366.6 440.9 600 800 1400 — — — 520.5 DCFUSE6S-900A DCFH-NH3
(1) Applied rating refers to the motor that is connected to the drive. For example, a D022 drive can be used in Normal Duty mode on a 15 Hp motor, or in Heavy Duty mode on a 10HP motor. A D014 drive can be used in Heavy Duty mode on a 7.5 Hp motor with the
same ratings as a D011 drive. The drive can be programmed for either mode. For any given catalog number, Normal Duty mode provides higher continuous current but smaller overload current compared to Heavy Duty mode. See parameter 0:36 [Duty Rating
Cfg].
(2) Only enclosure codes F, N, and R. See Product Rating Cross-reference on page 14
for frame sizes of other enclosure types.
(3) This drive is the next larger frame size.
(4) For UL compliance - fast-acting class J (Bussmann DFJ) or fast-acting class T (Bussmann JJS) fuses only. Equivalent fuses of class J, T may be used if they have lower I
peak
and I
2
t ratings than the Bussmann JJS fuse. For CE compliance - type gR fuses
(Bussmann 170M - size 00 to 3, IEC 60269 or DIN 43620, or FWP-_G10F, _G14F, _G22F) only. Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping. Max. source SCCR = 100 kA.
(5) For UL compliance - fast-acting class J (Bussmann DFJ) or fast-acting class T (Bussmann JJS) fuses only. Equivalent fuses of class J, T may be used if they have lower I
peak
and I
2
t ratings than the Bussmann JJS fuse. For CE compliance - type gR fuses
(Bussmann 170M - size 00 to 3, IEC 60269 or DIN 43620, or FWP-_G10F, _G14F, _G22F) only. Maximum protection device size is the highest rated device that supplies drive protection. Max. source SCCR = 100 kA.
(6) Circuit breaker - inverse time breaker - must be used with a fuse specified in the table. For US NEC, minimum circuit breaker size is 125% of motor FLA. Ratings that are shown are maximum values.
(7) Bulletin 140M/140MT with adjustable current range must have the current trip set to the minimum range so that the device does not trip.
(8) Bulletin 140M/140MT is UL Listed for 480Y/277V. Not UL Listed for use on 400V or 480V Delta/Delta, corner ground, or high-resistance ground systems.
(9) Bulletin 140M/140MT must be Frame C (140M-C2E-xxx or 140MT-C3E-xxx) or Frame D (140M-D8E-xxx or 140MT-D9E-xxx). Max. source SCCR = 65 kA.
(10) Bulletin 140M/140MT must be Frame D (140M-D8E-xxx or 140MT-D9E-xxx) or Frame F (140M-F8E-xxx). Max. source SCCR = 65 kA.
(11) When using the Bulletin 140M/140MT, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume that is specified in this column. Application-specific thermal considerations can require a larger enclosure.
(12) DC fuses specified are UL recognized and CE compliant.
480 Volt AC and 650 Volt DC Input Protection Devices—Drive Frames 1…7 (continued)
Applied
Rating
(1)
Frame
(2)
Cont.
Output
Amps
Sized For Normal Duty Sized For Heavy Duty Input Quantities AC Input Protection Devices
Input
Quantities
DC Input Protection
(12)
Cat. No.
Output Overload
Amps
Cat. No.
Output Overload
Amps
Cont. AC Input Fuse
Circuit Breaker
(6)
140M/140MT Type E Combination
Motor Controller with Adjustable
Current Range
(7)
(8)
Cont. DC
Input
Fuse Cat. No.
20-750-…
Fuse Holder
Cat. No.
20-750-…
Hp 1 Min 3 s 1 Min 3 s kVA Amps
Min [A]
(4)
Max [A]
(5)
Max [A]
Min. Encl.
Vol. [in.
3
]
Cat. No.
Min Enclosure
Volume [in.
3
]
(11)
Amps
480-Volt AC Input 650-Volt DC Input