Rockwell Automation Publication 750-IN119A-EN-P - April 2022 83
Chapter 5 Power Wiring
Power Jumper Wire Location and Connection Options—Frame 7
Frame 7 products use jumper wires to complete an electrical connection when
installed. Install or remove jumper wires according to the recommendations in
Table 13
.
MOV and AC EMI Capacitor PE-A Jumper—Frame 7
The PE-A jumper is located to the left of the AC input terminals.
Figure 53 - PE-A Jumper Positions—Frame 7
When the jumper wire is Connected (In), press the spade connector firmly
onto the sheet metal tab.
ATTENTION: Hazard of equipment damage exists if jumpers aren’t properly
disconnected. For Frame 7, secure the disconnected jumper wire to the
insulated position provided.
Disconnected (Out)