Hazardous locations certifications
Note
A certified isolating amplifier to IEC 60947-5-6 is required for intrinsic safety if the
NAMUR electronics is used in a hazardous area installation
A certified intrinsically safe barrier is required for intrinsic safety if the 8/16 mA
electronics is used in a hazardous area installation
North American and Canadian approvals
Factory Mutual (FM) explosion-proof approval
(See “Instructions for hazardous area installations (E5 and E6)” on page 19)
E5 Project ID: 3012658
Explosion-proof for Class I, Div. 1, Groups A, B, C, and D
Temperature Class: T6 (T
amb
–40 to 75 °C)
Enclosure: Type 4X
Factory Mutual (FM) intrinsically safe approval
(See “Instructions for hazardous (classified loc.) area installations (I5 and I6)” on page 21)
I5 Project ID: 3011456
Intrinsically Safe for Class I, Div. 1, Groups A, B, C, and D
Class I, Zone 0, AEx ia IIC
Temperature Code: (T
amb
–40 to 80 °C, T
proc
< 80 °C)
Control Drawing: 71097/1154 (with NAMUR electronics)
Control Drawing: 71097/1314 (with 8/16 mA electronics)
Canadian Standards Association (CSA) explosion-proof approval
(See “Instructions for hazardous area installations (E5 and E6)” on page 19)
E6 Project ID: 1786345
Explosion-proof for Class I, Div. 1, Groups A, B, C, and D
Temperature Class: T6 (T
amb
–40 to 75 °C)
Enclosure: Type 4X
Single Seal
Canadian Standards Association (CSA) intrinsically safe approval
(See “Instructions for hazardous (classified loc.) area installations (I5 and I6)” on page 21)
I6 Certificate Number: 06 CSA 1786345
Intrinsically Safe for Class I, Div. 1, Groups A, B, C, and D
Class I, Zone 0, Ex ia IIC
Temperature Code: T5 (T
amb
–40 to 80 °C, T
proc
< 80 °C)
Control Drawing: 71097/1179 (with NAMUR electronics)
Control Drawing: 71097/1315 (with 8/16 mA electronics)
Single Seal
Canadian Standards Association (CSA) non-incendive approval
(See “Instructions for hazardous (classified loc.) area installations (I5 and I6)” on page 21)
I6 Certificate Number: 06 CSA 1786345
Non-Incendive for Class I, Div. 2, Groups A, B, C, and D
Temperature Code: T5 (T
amb
–40 to 80 °C, T
proc
< 80 °C)
Control Drawing: 71097/1179 (with NAMUR electronics)
Control Drawing: 71097/1315 (with 8/16 mA electronics)
Single Seal