Advanced Program Group (continued)
Related Parameter(s): A418
54
Determines the bandwidth around A418 [Skip Frequency]. A419 [Skip Freq Band] is applied above and below the actual skip frequency. See
the diagram below.
A setting of 0.0 disables this parameter.
Values
Default
0.0Hz
Min/Max:
0.0/30.0 Hz
Display:
0.1 Hz
A424 [DC Brake Time]
Related Parameter(s): P107, A425
Sets the length of time that DC brake current is “injected” into the motor. Refer to parameter A425 [DC Brake Level].
Values
Default
0.0 Secs
Min/Max:
0.0/99.9 Secs (A setting of 99.9 = Continuous)
Display:
0.1 Secs