EasyManua.ls Logo

Saftronics HPVFE - Basic Program Group Parameters; Motor Nameplate Data Setup; Frequency Limit Setup

Saftronics HPVFE
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Basic Program Group
Sailer Manual HPVFE
39
P101 [Motor NP Volts]
Related Parameter(s): d004, A453
Stop drive before changing this parameter.
Set to the motor nameplate rated voltage.
Values
Default
Based on Drive Rating
Min/Max:
20/Drive Rated Voltage
Display:
1 VAC
P102 [Motor NP Hertz]
Related Parameter(s): A453, A444
Stop drive before changing this parameter.
Set to the motor nameplate rated frequency.
Values
Default
60 Hz
Min/Max:
10/400 Hz
Display:
1 Hz
P103
[Motor OL Current]
Related Parameter(s): P111, t221, A441, A444, A448, A437
Set to the maximum allowable motor current.
The drive will fault on an F7 Motor Overload if the value of this parameter is exceeded by 150% for 60 seconds or 200% for 3 seconds.
Values
Default
Based on Drive Rating
Min/Max:
0.0/(Drive Rated Amps
2)
Display:
0.1 Amps
P104 [Minimum Freq]
Related Parameter(s): d001, d002, d013, P105, t211, t213, A438
Sets the lowest frequency the drive will output continuously.
Values
Default
0.0 Hz
Min/Max:
0.0/400.0 Hz
Display:
0.1 Hz
P105 [Maximum Freq]
Related Parameter(s): d001, d002, d013, P104, A404, t212,
t214, A438
Stop drive before changing this parameter.
Sets the highest frequency the drive will output.
Values
Default
60 Hz
Min/Max:
0/400 Hz
Display:
1 Hz

Related product manuals