Page #33 background imageLoading...
Page #33 background image
8000m Series
- 32 -
Function
Code
Function Descriptions
Minimum
Unit
Factory
Setting
Modifica-
tion Type
F0.12
Upper limit
frequency
F0.14~ F0.10 0.01Hz 50.00Hz
F0.13 Reserved
F0.14
Lower limit
frequency
0.00Hz~ F0.12 0.01Hz 0.00Hz
F0.15
The function of
lower limit
frequency
0 : Running at lower limit
frequency
1: Stop frequency point
2: Sleep frequency point
0
F0.16
Carrier frequency
setting
1.0~15.0kHz 1kHz
Different
according
to the
inverter
type
F0.17
PWM mode
selection
0:PWM mode 1
1:PWM mode 2
2:PWM mode 3
0
F0.18
Acceleration time
1
0.1~3600.0s 0.1s
Different
according
to the
inverter
type
F0.19
Deceleration time
1
0.1~3600.0s 0.1s
Different
according
to the
inverter
types
F0.20
Default setting
restoring
0: No operation
1: Restore to factory setting
2: Fault record clearing
0
F0.21
Parameter lock and
unlock
0: Unlock parameter
1: Lock parameter
0