8000m Series
- 33 -
Function
Code
Function Descriptions
Minimum
Unit
Factory
Setting
Modifica-
tion Type
F0.22~
F0.24
Reserved
F0.25
Cooling fan
running method
0: Keep running when power on
1: Reserved
1
F1 Group: Start and Stop Parameters
F1.00 Start mode
0:Start directly
1:DC braking first and then start
2:Speed tracing and start
0
F1.01 Start frequency 0.00~10.00Hz 0.01Hz 1.50Hz
F1.02
Hold time of start
frequency
0.0~50.0s 0.1s 0.0s
F1.03
DC braking current
before start
0.0~150.0% 0.10% 0.00%
F1.04
DC braking time
before start
0.0~50.0s 0.1s 0.0s
F1.05 Stop mode
0: Deceleration to stop
1: Coast to stop
0
F1.06
Trigging frequency
of DC braking at
stop
0.00~ F0.10 0.01Hz 0.00Hz
F1.07
Waiting time
before DC braking
at stop
0.0~50.0s 0.1s 0.0s
F1.08
DC braking current
at stop
0.0~150.0% 0.10% 0.00%
F1.09
DC braking time at
stop
0.0~50.0s 0.1s 0.0s
F1.10
Dead time between
FWD and REV
0.0~3600.0s 0.1s 0.0s
F1.11 Terminals control 0: Disabled 1