EasyManua.ls Logo

SAJ 8000m Series

SAJ 8000m Series
153 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8000m Series
- 33 -
Function
Code
Function Descriptions
Minimum
Unit
Factory
Setting
Modifica-
tion Type
F0.22~
F0.24
Reserved
F0.25
Cooling fan
running method
0: Keep running when power on
1: Reserved
1
F1 Group: Start and Stop Parameters
F1.00 Start mode
0:Start directly
1:DC braking first and then start
2:Speed tracing and start
0
F1.01 Start frequency 0.00~10.00Hz 0.01Hz 1.50Hz
F1.02
Hold time of start
frequency
0.0~50.0s 0.1s 0.0s
F1.03
DC braking current
before start
0.0~150.0% 0.10% 0.00%
F1.04
DC braking time
before start
0.0~50.0s 0.1s 0.0s
F1.05 Stop mode
0: Deceleration to stop
1: Coast to stop
0
F1.06
Trigging frequency
of DC braking at
stop
0.00~ F0.10 0.01Hz 0.00Hz
F1.07
Waiting time
before DC braking
at stop
0.0~50.0s 0.1s 0.0s
F1.08
DC braking current
at stop
0.0~150.0% 0.10% 0.00%
F1.09
DC braking time at
stop
0.0~50.0s 0.1s 0.0s
F1.10
Dead time between
FWD and REV
0.0~3600.0s 0.1s 0.0s
F1.11 Terminals control 0: Disabled 1