EasyManuals Logo

SAJ 8000m Series User Manual

SAJ 8000m Series
153 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #49 background imageLoading...
Page #49 background image
8000m Series
- 48 -
Function
Code
Function Descriptions
Minimum
Unit
Factory
Setting
Modifica-
tion Type
F9.13
PID wake-up
threshold
0.0~100.0% 0.10% 0.00%
F9.14
PID wake-up
detecting delay
time
0.0~3600.0s 0.1s 3.0s
F9.15
Lower retaining
frequency of PID
sleep detecting
0.00Hz~20.00Hz 0.01Hz 10.00Hz
F9.16
PID Lower
retaining
frequency running
time
0.0~3600.0s 0.01s 10.0s
F9.17~F
9.18
Reserved
FA Group: Protection and Malfunction Parameters
FA.00
Motor overload
protection
0: Protection Disabled
1: Normal motor with low speed
compensation
2: Variable frequency motor
without low speed
compensation
2
FA.01
Motor over load
protection current
20.0%~120.0% (motor rated
current)
0.10% 100.00%
FA.02
Threshold for
frequency reducing
at instantaneous
power failure
70.0%~110.0% (standard bus
voltage)
0.10% 80.00%
FA.03
Frequency
reducing rate at
instantaneous
power failure
0.00Hz~F0.10 0.01Hz 0.00Hz
FA.04
Over-voltage
stalling protection
0:Disabled
1:Enabled
0