Function
Code
Function Descriptions
Minimum
Unit
Factory
Setting
Modifica-
tion Type
FA.05
Over-voltage
stalling protection
point
110~150% 1% 120%
FA.06
Auto current
limiting level
50~200% 1% 160%
FA.07
Frequency
decrease rate
during current
limiting
0.00~50.00Hz/s 0.01Hz/s
10.00Hz/
s
FA.08
Auto current
limiting selection
0:Enabled
1: Disabled at constant speed
1
FA.09
Fault auto-reset
times
0~3 0
FA.10
Fault auto-reset
interval
0.1~100.0s 0.1s 1.0s
FA.11 Reserved
FA.12
Phase-lack
protection of input
0:Disabled
1:Enabled
1
FA.13
Phase-lack
protection of
output
0: Disabled
1:Enabled
1
FA.14
Fault type last two
time
0: No fault
1: Inverter module fault
(E001)
2. Over-current during
acceleration
(E002)
3: Over-current during
deceleration
(E003)
4: Over-current at constant
FA.15 Fault type last time