EasyManuals Logo

SAJ 8000m Series User Manual

SAJ 8000m Series
153 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #50 background imageLoading...
Page #50 background image
8000m Series
- 49 -
Function
Code
Function Descriptions
Minimum
Unit
Factory
Setting
Modifica-
tion Type
FA.05
Over-voltage
stalling protection
point
110~150% 1% 120%
FA.06
Auto current
limiting level
50~200% 1% 160%
FA.07
Frequency
decrease rate
during current
limiting
0.00~50.00Hz/s 0.01Hz/s
10.00Hz/
s
FA.08
Auto current
limiting selection
0:Enabled
1: Disabled at constant speed
1
FA.09
Fault auto-reset
times
0~3 0
FA.10
Fault auto-reset
interval
0.1~100.0s 0.1s 1.0s
FA.11 Reserved
FA.12
Phase-lack
protection of input
0:Disabled
1:Enabled
1
FA.13
Phase-lack
protection of
output
0: Disabled
1:Enabled
1
FA.14
Fault type last two
time
0: No fault
1: Inverter module fault
(E001)
2. Over-current during
acceleration
(E002)
3: Over-current during
deceleration
(E003)
4: Over-current at constant
FA.15 Fault type last time

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SAJ 8000m Series and is the answer not in the manual?

SAJ 8000m Series Specifications

General IconGeneral
BrandSAJ
Model8000m Series
CategoryController
LanguageEnglish

Related product manuals