- 40 -
Function
Code
Parameter Name
Setting Range
Default
Property
Address
(HEX)
FA.09
DO action during fault
auto reset
0: No act
1: Act
0
0A09
FA.10
Time interval of fault auto
reset
0.1s 100.0s
1.0s
0A0A
FA.11
Input phase loss
protection
0: Disabled
1: Enabled
1
0A0B
FA.12
Output phase loss
protection
0: Disabled
1: Enabled
1
0A0C
FA.13
Fault protection action
selection 1
0: Free stopping
1: Stop according to the stop mode
2: Continue to run
Single-digit: Motor overload (Err11)
Ten’s digit: Input phase loss (Err12)
Hundred’s digit: Output phase loss (Err13)
Thousand’s digit:External equipment fault
(Err15)
Ten thousand’s digit: Communication fault
(Err16)
0
0A0D
FA.14
Reserved
-
-
-
0A0E
FA.15
Fault protection action
selection 3
0: Free stopping
1: Stop according to the stop mode
2: Continue to run
Single-digit: User-defined fault 1 (Err27)
Ten’s digit: User-defined fault 2 (Err28)
Hundred’s digit: Reserved
Thousand’s digit:Drop (Err30)
Ten thousand’s digit: PID feedback loss at
run
time (Err31)
0
0A0F
FA.16
Reserved
-
-
-
0A10
FA.17
Reserved
-
-
-
0A11
FA.18
Undervoltage setting
60.0% 140.0%
100.00%
0A12
FA.19
Overvoltage setting
200.0V 810.0V
810.0V
0A13
FA.20
Continuerunning
frequency
selection
during failure
0: Run with the current run frequency
1: Run with the setting frequency
2: Run with the upper limit frequency
3: Run with lower limit frequency.
4: Run with standby frequency when
abnormal
0
0A14
FA.21
Abnormal standby
frequency setting
0.0%
100.0%(Current target frequency)
100.00%
0A15
FA.22
Action selection at
instantaneous power
failure
0: Invalid
1: Slow down
2: Deceleration stop
0
0A16
FA.23
Action pause judging
80.0% 100.0%
90.00%
0A17