032
4.1 Function Code
F0 Group - Basic Run Parameters
Function
Code
Name Set Range
Minimum
Unit
Factory
Default
Modi󽗉cation
F0.10 Digital set 1 control
LED ones digit: power down
storage
0: storage
1: not storage
LED tens digit: hold when stop
0: hold
1: not hold
LED hundred digit: ▲ / key,
UP/DOWN frequency
0: invalid
1: valid
LED thousands digit: reserved
1 000
F0.11 Digital set 2 control 1 000
F0.12
Frequency source
digital setting 1
0.00Hz ~【F0.16】upper limit
of frequency
0.01Hz 50.00
F0.13
Frequency source
digital setting 2
0.00Hz ~【F0.16】upper limit
of frequency
0.01Hz 50.00
F0.14
Auxiliary frequency
source weight
coe󽗋cient K setting
0.01 10.00 0.01 1.00
F0.15
Maximum output
frequency
Low frequency range: MAX
{50.00, 【F0.16】}~ 300.00
High frequency range: MAX
{50.00, 【F0.16】}~ 3000.0
0.01Hz 50.00 ×
F0.16
Upper limit
frequency
【F0.17】~【F0.15】 0.01Hz 50.00 ×
F0.17
Lower limit
frequency
0.00Hz ~【F0.16】 0.01Hz 0.00 ×