033
4.1 Function Code
F0 Group - Basic Run Parameters
Function
Code
Name Set Range
Minimum
Unit
Factory
Default
Modi󽗉cation
F0.18
Frequency output
mode
0: low frequency mode
(0.00 300.00Hz)
1: high frequency mode
(0.0 3000.0Hz)
Note: high frequency mode is
only e󽗈ective to VF control
1 0 ×
F0.19 Acceleration time 1
0.1 ~ 3600.0s
0.4 ~ 4.0KW 7.5s
5.5 ~ 30.0KW 15.0s
37.0 ~ 132.0KW 30.0s
160.0 ~ 630.0KW 60.0s
0.1s
Depending
on model
F0.20 Deceleration tima 1 0.1s
Depending
on model
F0.21 Running direction
0: forward
1: reverse
2: prevent reversing
1 0 ×
F0.22 Carrier frequency
1.0 16.0KHz
0.4 4.0KW 6.0KHz
1.0 16.0KHz
5.5 30KW 4.0KHz
1.0 16.0KHz
37 132KW 2.5KHz
1.0 10.0KHz
160 630KW 1.5KHz
1.0 5.0KHz
0.1KHz
Depending
on model
F0.23 User password
1: 0 9: no password
protection
2: The password setting is
successful and will take 3
minutes to take e󽗈ect
3: Write protection is not
valid for this parameter and
cannot be initialized
1 0