F5 Group - VF Control Parameters
Function
Code
Name Set Range
Minimum
Unit
Factory
Default
Modication
F5.17
VF curve max.
voltage of half
separation mode
0.0 ~ 100.0%*rated voltage of motor
note: this voltage represents output
voltage of VFD
0.1% 80.0% ×
F5.18
controller
adjustment cycle
of voltage closed
loop output
0.01 ~ 10.00s 0.01s 0.10 ×
F5.19 Voltage rising time
0.1 ~ 3600.0s
note: this parameter is only valid for
open loop output mode of complete
separated voltage
0.1s 10.0 ○
F5.20
Voltage declining
time
0.1s 10.0 ○
F5.21
Voltage feedback
disconnection
treatment
0: alarm and keep running with the
voltage of disconnection
moment
1: alarm and keep running with
decreased voltage of amplitude
limiting value
2: protection action and free stop
1 0 ×
F5.22
Detection value of
voltage feedback
disconnection
0.0 ~ 100.0%*rated voltage of motor 0.1% 2.0% ○
F5.23
Detection time of
voltage feedback
disconnection
0.0 ~ 100.0s 0.1s 10.0 ○
F5.24
Limit voltage of
voltage feedback
disconnection
0.0 ~ 100.0%*rated voltage of motor
note: this voltage represents
the output voltage of VFD, and
reasonable setting of this parameter
could prevent machine damage
resulting from voltage overshoot at
disconnection moment.
0.1% 80.0% ○
4.1 Function Code