6-2 EB 8091 EN
Start-up
Before start-up or putting the valve back into
service, make sure the following conditions
are met:
The valve is properly installed into the
pipeline (see the 'Installation' section).
The leak and function tests have been
completed successfully (see the 'Testing
the installed valve' section).
The prevailing conditions in the plant
section concerned meet the valve sizing
requirements (see information under 'In-
tended use' in the 'Safety instructions
and measures' section).
6.1 Supply pressures
The maximum permissible supply pressure
depends on the fail-safe position (see the
'Design and principle of operation' section):
a) Fail-safe position "Actuator
stem retracts"
(specications in bar)
Bench range Adjusted to
Max.
permissible
supply
pressure
0.2 to 1 0.4 to 0.8 2.5
0.4 to 2.0 0.8 to 1.6 3.3
1.4 to 2.3 1.7 to 2.1 3.8
2.1 to 3.3 2.4 to 3.0 4.7
b) Fail-safe position"Actuator
stem extends"
Max. permissible supply pressure: 4bar
6.2 Putting the control valve
(back) into operation
1. Allow the valve to cool down or warm up
to reach ambient temperature before
start-up when the ambient temperature
and process medium temperature differ
greatly or the medium properties require
such a measure.
2. Slowly open the shut-off valves in the
pipeline. Slowly opening these valves
prevents a sudden surge in pressure and
high ow velocities which can damage
the valve.
3. Check the valve to ensure it functions
properly.