Fault/diagnostic alarm
Default setting acc. to Pro
-
file 3.01 Condensed Status
Classified
Diagnosis
Yes No
Initialization running
0xA4
GOOD_MAINT_REQ
Hardware error
x signal
0xA8
GOOD_MAIN_DEMANDED
DIA_MEASUREMENT
i/p converter
0x24
BAD_MAINT_ALARM
DIA_HW_ELECTR
Hardware
0x24
BAD_MAINT_ALARM
DIA_HW_ELECTR
Data memory
0xA4
GOOD_MAINT_REQ
DIA_MEM_CHECKSUM
Test calculation
0x24
BAD_MAINT_ALARM
DIA_MEM_CHECKSUM
Program loading error
0x24
BAD_MAINT_ALARM
DIA_MEM_CHECKSUM
Data error
Control parameter
0xA4
GOOD_MAINT_REQ
DIA_MEM_CHECKSUM
Potentiometer parameter
0xA4
GOOD_MAINT_REQ
DIA_MEM_CHECKSUM
Calibration error
0xA4
GOOD_MAINT_REQ
DIA_MEM_CHECKSUM
Interal device error
0xA4
GOOD_MAINT_REQ
DIA_MEM_CHECKSUM
General parameters
0xA4
GOOD_MAINT_REQ
DIA_MEM_CHECKSUM
Options parameters
0xA4
GOOD_MAINT_REQ
DIA_MEM_CHECKSUM
Info parameter
0xA4
GOOD_MAINT_REQ
DIA_MEM_CHECKSUM
PA parameter
0xA4
GOOD_MAINT_REQ
DIA_MEM_CHECKSUM
Diagnostic parameter
0xA4
GOOD_MAINT_REQ
DIA_MEM_CHECKSUM
Extended diagnostics EXPERTplus
Air supply
Perhaps modified (TEST)
0x80 GOOD_NON_SPECIFIC
Perhaps not enough (TEST)
0x80 GOOD_NON_SPECIFIC
Perhaps not enough
0x80 GOOD_NON_SPECIFIC
Working at full capacity
0x80 GOOD_NON_SPECIFIC
Working at full capacity (TEST)
0x80 GOOD_NON_SPECIFIC
Perhaps modified
0x80
GOOD_NON_SPECIFIC
Actuator springs
Perhaps spring stiffness reduced (TEST)
GOOD_NON_SPECIFIC
26 KH 8384-4 EN
Measured value status and valve diagnostics