EasyManua.ls Logo

Samson 3767 - Operation; Tuning the Positioner Mounted onto the Control Valve

Samson 3767
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38 EB8355-2EN
Operation
5 Operation
5.1 Tuningthepositioner
mountedontothecontrol
valve
Startingpointandreferencevariable
When adjusting the positioner directly at the
controlvalve,thetravel(openingangle)must
beadaptedtothereferencevariable.
Withareferencevariable,forexample,4to
20mA,thevalvemustmovethroughitsen-
tiretravelrangefrom0to100%(Fig.13,
left).
For positioners for rotary actuator, an open-
ingangle,forexample,0to70°mustbeas-
signedtothereferencevariable.
ThestartingpointisbasedontheCLOSED
position of the valve.
Depending on the actuator version ("actua-
torstemextends"or"actuatorstemretracts")
and the operating direction of the positioner
(>>or<>),thisstartingpointcanbeeither
thelowerorupperrangevalue(4or20mA)
ofthereferencevariable.
Thereferencevariablerangeandthusthe
upper range value determine the travel of
the valve.
Insplit-rangeoperation(Fig.13,right),the
control valves work with smaller reference
variableranges.Thecontrolleroutputsignal
is used to control two control valves, dividing
it such that the valves move through their en-
tire travel range at half the input signal
rangeeach(e.g.rstvalvesetto4to
12mA,secondvalvesetto12to20mA).To
avoidoverlapping,allowforadeadbandof
±0.5mAasshowninFig.13.
The startingpoint(zero)isadjustedatthe
zero adjuster (6.2); the span, i.e. the upper
range value, is adjusted at the span adjuster
(6.1).
Duringtheadjustment,connectasuitable
ammeter to the signal input and apply air to
the supply air input.
NOTICE
When the positioner is controlled by
a computer whose signal is limited,
e.g. between 4 to 20mA, set the po-
sitioner to the range from 4.5 to
20mA.
This is the only way to ensure that the
actuator is completely vented and the
valve completely closed when the
controller issues a 4mA signal.
For operating direction <>, set the
range to 4 to 19.5mA.

Other manuals for Samson 3767

Related product manuals