EasyManua.ls Logo

Samson 4763 - Page 30

Samson 4763
78 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-8 EB 8359-2 EN
Installation
With a set point, for example 4 to 20mA,
the valve must move through its entire travel
range from 0 to 100%. The starting point
then is 4mA and the upper range value
20mA.
In split-range operation, the controller output
signal is used to control two control valves,
dividing it such that the valves move through
their entire travel range at half the input sig-
nal range each (e.g. rst valve set to 4 to
12mA, second valve set to 12 to 20mA). To
avoid overlapping, allow for a dead band of
± 0.5mA as shown in Fig.5-8.
The starting point (zero) is adjusted at the
screw (4); the set point span, i.e. the upper
range value, is adjusted at the pin (2).
Exchanging the range spring (Fig.5-9)
Î Unscrew screw (7) on the range spring.
Undo hex socket screw (5) and pull out
the lever together with shaft.
Î Exchange range spring. Slide lever with
shaft through sleeve (3), positioner hous-
ing and bracket (6.1).
Î Secure range spring with the screw (7).
Î Move bracket and shaft until the screw
(5) sits on the attened part of the shaft.
Î Tighten screw (5). Allow for a play of
0.05 to 0.15mm between the lever (1)
and the sleeve (3) as well as between the
range spring (6) and the positioner hous-
ing.
4
21 14 13 10.2 7
1
15
8
5 6.1 63
Fig.5-9: Positioner with cover removed

Table of Contents

Other manuals for Samson 4763

Related product manuals