EasyManua.ls Logo

Samsung AVXTJH028EE - Page 155

Samsung AVXTJH028EE
508 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Samsung Electronics 4-64
4-5-5 Indoor Heat Exchanger's EVAP IN sensor dislocation error
(Operation)

(Timer)

(Fan)

Filter)

(Defrost)
t Indoor heat exchanger's EVAP IN piping sensor has been dislocated
t Refer to how to determine below
Indoor unit display
Criteria
Cause of problem
Outdoor unit display
1. How to diagnose
1) During Cooling Operation
x x x
(
x x x
:
The address of the error occurred indoor unit)
Tcond, out - Tair, out > 3°C OK
Tair, in - Teva, out > 4°C NO
Tair, in - Teva, out > 4°C OK
Compressor in operation &
Indoor unit operation & Thermo On
OK
Error details
Indoor heat exchanger's
EVAP IN sensor dislocation error
2) During heating operation
Average high pressure > 25kg/
OK
Average low pressure > 8.5kg/
OK
Tcond, out - Tair, out ≥ 3°C OK
Tair, in - Teva, out ≥ 2°C NO
Tcond, out - Tair, out < -2°C OK
Compressor in operation &
Indoor unit operation & Thermo On
OK
Error details
Indoor heat exchanger's
EVAP IN sensor dislocation error
2. How to check
Check if an Indoor heat exchanger's EVAP IN sensor has been dislocated then is correct after assembling.
$9;&6+B$BaLQGG 

Table of Contents

Related product manuals