Troubleshooting
Samsung Electronics 4-100
4-5-41 Compressor Discharge Temperature Sensor Breakaway Error
1. Inspection Method
Yes
Yes
Are the discharge sensor
and the sensor holder accurately attached?
Is the sensor resistance
maintaining an optimal value?
Is the compressor operating
normally and is the temperature of
the compressor discharge pipe maintaining
an optimal temperature?
Execute check-up after restarting operation.
Re-insert the sensor.
Re-attach the sensor holder.
Yes
No
Compressor non-operation cause analysis
No
Faulty sensor
Change the sensor.
No
Outdoor Unit Display
(No. 1 compressor for each outdoor unit), (Compressor No. 2),
(Compressor No. 3),
Indoor Unit Display
×(Operation)
(Reservation) (Blast) (Filter) ×(Defrost)
Judgment Method
1) Current value of the relevant compressor (CT sensor Value ) is 5A or more.
2) Discharge Temperature of Relevant Compressor < High Pressure Saturation Temperature Conditions 1 and 2
above are continuously checked for more than 30 minutes