4-5-43 : Suction Temperature Sensor Breakaway Error
Indoor Unit Display
×(Operation)
(Reservation) (Blast) (Filter) ×(Defrost)
Judgment Method
Special Cause
t*GUIFTVDUJPOUFNQFSBUVSFSJHIUCFGPSFPQFSBUJOHUIF$0.1XIFOUIFPQFSBUJOHPSEFSJTUIFIJHIFTUJTTFUBU
Tsuc, ini, and the suction temperature of the current COMP is set at Tsuc, real, it is considered to have an error if
the condition of |Tsuc,real < Tsuc,ini| < 2°C is maintained for 30 minutes.
t4VDUJPOUFNQFSBUVSFTFOTPSCSFBLBXBZGBVMUZTFOTPS
Outdoor Unit Display
1. Inspection Method
Complete
Is suction sensor and sensor
Holder accurately attached?
Is suction sensor
resistance value reasonable?
(Ref: E231 )
Faulty Sensor : Change sensor
No
Re-insert the sensor.
Re-attach the sensor holder.
No
Yes
Yes