4st Edition of TEMI2000_Series IM : Aug. 18. 2009 Page 31 / 55
5.2 REPEAT function
Press [REPEAT SET] button on PROGRAM SET menu screen to enter into this screen.
This screen is to set repeat operation of entire current pattern and partial segment operation after
complete of current operation.
Setup box to input pattern number for repeat operation.
Setup box to input count number for current entire pattern repeat.
Setup box to input next pattern number to run continually after complete of current operation.
Setup box to input start segment number for partial repeat operation.
Setup box to input end segment number for partial repeat operation.
Setup box to input count number for partial repeat operation.
Displays of experiment name for current pattern.
The experiment name can be set at [5.6 PATTERN NAME].
This Displays is just READ ONLY and cannot be changed on this screen.
Button to set PATTERN END MODE for operation state after complete of operation.
RESET : Make program operation STOP with generating PTEND signal.
SEG HOLD : Stay operation run with holding SP at last segment.
LINK RUN : Resume pattern operation number set as LINK PATTERN.
Table 5-2. REPEAT SET Parameters
Parameter Range Unit Default
PATTERN NUMBER 1~120 ABS 1
REPEAT COUNT 0(infinite)~999 ABS 1
LINK PATTERN 1~120 ABS 1
PATTERN END MODE STOP, SEG HOLD, LINK RUN ABS STOP
START SEG. for Partial repeat 0~99 ABS 0
END SEG. for Partial repeat 0~99 ABS 0
REPEAT COUNT
for Partial repeat
0~99 ABS 0
[Figure 5-3] REPEAT SET screen