18 S&C Instruction Sheet 461-502
Operation
Additional Screens
Figure 26 on pages 18 and 19 shows additional screens that can be added to the display screens using the TripSaver II
Service Center Conguration Software.
Screen Name Description
Secondary Normal Screen
(O: VI Open)
Three operating parameters are displayed: Vacuum interrupter status at
the upper left corner (symbol “O” for open, symbol “I” for closed); number
of Open operations at the upper right corner; and remaining contact wear
in bar chart format at the bottom of the screen. (A full blue bar indicates
100% remaining contact wear. The blue bar shortens in length leftward as
remaining contact wear decreases.)
(I: VI Closed)
Blue Screen A blue screen is displayed.
Vacuum Interrupter Status The status of the vacuum interrupter: either OPEN or CLOSED is
displayed.
Mode Selector Status The mode of operation: either AUTO or NR is displayed.
TCC #0 (Initial Trip) The short name for the initial trip curve is displayed.
Figure 26. Additional available screens.
FIGURE CONTINUED