14
230 V Single-phase 60 Hz
Model STW0922C2 / STW0923C2 / STW0925C2
Cooling & Electric Heating Models
y
RATING CAPACITY: 9,100 BTU/h AIR FLOW RATE: 315 CFM
EVAPORATOR CONDENSER
ENT. TEMP. °F (°C) AMBIENT TEMP. °F (°C)
W.B. D.B. 75 85 95 105 115
(23.9) (29.4) (35.0) (40.6) (46.1)
TC 9,220 8,770 8,260 7,690 7,050
CI 0.55 0.6 0.65 0.75 0.85
72 (22.2) SHC 7,160 6,950 6,710 6,440 6,150
59 76 (24.4) SHC 8,190 7,970 7,730 7,470 7,050
(15.0) 80 (26.7) SHC 9,220 8,770 8,260 7,690 7,050
84 (28.9) SHC 9,220 8,770 8,260 7,690 7,050
88 (31.1) SHC 9,220 8,770 8,260 7,690 7,050
TC 9,560 9,140 8,680 8,160 7,600
CI 0.55 0.61 0.66 0.76 0.86
72 (22.2) SHC 5,950 5,760 5,560 5,340 5,110
63 76 (24.4) SHC 6,970 6,790 6,590 6,360 6,130
(17.2) 80 (26.7) SHC 8,040 7,860 7,660 7,430 7,200
84 (28.9) SHC 9,070 8,880 8,680 8,160 7,600
88 (31.1) SHC 9,560 9,140 8,680 8,160 7,600
TC 9,930 9,540 # 9,100 8,620 8,090
CI 0.56 0.61 0.67 0.77 0.87
72 (22.2) SHC 4,730 4,580 4,400 4,210 4,010
67 76 (24.4) SHC 5,760 5,600 5,420 5,240 5,030
(19.4) 80 (26.7) SHC 6,830 6,670 6,490 6,310 6,100
84 (28.9) SHC 7,850 7,690 7,520 7,330 7,120
88 (31.1) SHC 8,870 8,720 8,540 8,350 8,090
TC 10,460 10,090 9,700 9,270 8,800
CI 0.57 0.62 0.68 0.78 0.88
72 (22.2) SHC 3,510 3,380 3,240 3,080 2,910
71 76 (24.4) SHC 4,540 4,400 4,260 4,100 3,940
(21.7) 80 (26.7) SHC 5,610 5,470 5,330 5,170 5,010
84 (28.9) SHC 6,630 6,490 6,350 6,200 6,030
88 (31.1) SHC 7,650 7,520 7,380 7,220 7,060
TC 10,670 10,320 9,960 9,540 9,090
CI 0.58 0.63 0.69 0.79 0.9
75 76 (24.4) SHC 3,250 3,130 3,010 2,880 2,730
(23.9) 80 (26.7) SHC 4,320 4,200 4,080 3,950 3,800
84 (28.9) SHC 5,340 5,220 5,110 4,970 4,820
88 (31.1) SHC 6,360 6,250 6,130 5,990 5,850
TC : Total Cooling Capacity (BTU/h)
SHC: Sensible Heat Capacity (BTU/h)
CI : Compressor Input (kW)
Rating conditions are M.R.= 2.38 US pints/h
: Outdoor Ambient Temp. 95°F DB
: Indoor Unit Entering Air Temp. 80°F DB / 67°F WB

Other manuals for Sanyo STW-2 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sanyo STW-2 Series and is the answer not in the manual?

Sanyo STW-2 Series Specifications

General IconGeneral
BrandSanyo
ModelSTW-2 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals