BACNET
OBJECT
ID
BACNET OBJECT
NAME
DESCRIPTION /
RANGE
UNIT
DEFAULT
VALUE
READ/
MODBUS
WRITE ID
NOTE
AV46
CO2 or
Termperature
set point (for ai1
set point)
0-3276
-
1000
-
R46
-
AV47
CO2 PID
parameter- Kp
(for ai1)
0-3276
0
20
R
R47
(HMI)
-
AV48
CO2 PID
parameter- Ki
(for ai1)
0-3276
-
-
R
R48
(HMI)
-
AV49
CO2 value(for
ai1 or HMI CO2)
0-9999
-
-
R
R49
-
AV50
ai1 for 0-10 v
(CO2 or
Temperature
sensor) input
0-10
Vtg
AV51-
AV52
R
R50
-
AV51
ai1 for (Co2
sensor or
Temperature)
input scale min.
0-AV52
PPM
40
RW
R51
-
AV52
ai1 for (Co2
sensor or
Temperature)
input scale
max.
AV52-9999
PPM
200
RW
R52
-
AV57
Air f low PID
output
Internal use
-
-
R
R57
-
AV58
Cooling temp
setpoint+DB
Internal use
-
-
R
R58
-
AV59
heating temp
setpoint- DB
Internal use
-
-
R
R59
-
AV60
Ai0 mode
select
0=not use,
1=Occupied,
Unoccupied2=NTC
thermistor
-
0
R
R60
-
AV61
Current VAV
position
feedback (0-
100)
0-100
%
-
R
R61
-
AV62
Damper min.
position
selection
Internal use
Pa
-
R
R62
-
AV63
Cooling set
point
Internal use
-
-
R
R63
-
AV64
HMI Temp.
display-
Fahrenheit
Internal use
°F
-
-
-