Page 13 of 45
4 Configuration the VAV Box and Actuators
4.1 Maintenance
Our actuators are maintenance-free. If necessary, please clean it with a dry cloth on the surface
cover.
4.2 Changing the Temperature Set-points And Limits
Changing the ASV305BF7XXXW VAV actuators user functions with EY-RU305F700XW series
thermostats are limited to active setpoint of the room and occupancy mode.
Quick start to change set points:
1.
Press Up or down to change the temperature setpoint.
2.
Press the [power] button to change the occupancy mode.
To Enter the admin mode, press the “UP” and “DOWN” button together and hold for 3 seconds.
You may need a password to enter.
4.3 Configuring the VAV Box Options
The configurations of the functions that are accessible through an EY-RU305F700XW series room
thermostat. The values and setting that are entered during the installation and commissioning of a
VAV terminal unit can be set via 3 ways. Typically, most of the functions do not need to change
after the installation and commissioning process.
To set up the configuration function, you will need the following items and information.
•
Details about the VAV terminal unit. Example size, inlet diameter and max/min airflow.
•
An EY-RU305F700XW series thermostats, BMS system or a PC to be use as a
configuration tool.
•
The Building automation system configurations and setting for the network.
Please take note that not all functions are available on every model of the ASV305BF7XXXW VAV
controller.