7.2 Electronic issues and their solution
Pressing the start button the system starts but goes into alarm after about 20-25 seconds.
Check if the watermaker is in hydraulic block (pressure indicated by the pressure gauge above 9-10 bar and
pump start/stop continuously). In this case, carry out the reset procedure indicated in the manual and restart
the system.
If the system still does not start (it goes on the block after about 20 seconds), activate the system
manually by inserting the bypass.
If the system works correctly (normal pressure/normal output) it could be just a probe issue. In this
case disconnect the 2 cables of the pressure switch from the PCB of the controller, then connect
the 2 cables to a meter in ohm position. The pressure switch must give, under normal conditions,
a closing signal followed by an opening signal, every 3-4 seconds. If the signal is always open or
always closed, the pressure switch must be replaced