EasyManua.ls Logo

Schlage AD400 - Updating or Expanding Existing Systems; ADDING Ad400 S to an Existing Legacy System; ADDING Ad300 S to an Existing Ad400 System

Schlage AD400
42 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.4 UPDATING OR EXPANDING EXISTING SYSTEMS
NOTICE: Legacy Wireless 485-PIM-ODT & WAPMs are still supported in SG 10.2; however the Galaxy
CPU must be flashed up to 5.0 if you are upgrading from SG 8 or 9, you may want to contact dealer
technical support to ensure you properly step through the hardware flash upgrade.
1.4.1 ADDING AD400’S TO AN EXISTING LEGACY SYSTEM
a) DEDICATED NETWORK: You can install AD400 wireless hardware onto a separate DSI section. In this case
you must configure the Serial Channel programming (in SG software) to use the Network Type = AD400
(wireless only) for the both new AD400 network bus as well as the legacy Schlage ODT bus. The addressing
requirements must meet specifications see the following sections on addressing AD400 PIMs and Readers.
b) SHARED NETWORK: You can install the AD400 wireless hardware onto the same network bus with the
existing legacy PIMs and Readers as long as you do the following:
You must assign unique AD400 PIM addresses that do not duplicate the ODT PIM addresses.
You must assign unique addresses to AD400 Readers that do not duplicate the legacy readers on the
network bus.
You cannot cross-link the equipment: Legacy readers can only link to legacy PIMs and visa-versa, AD400
readers can only link to AD400 PIMs.
You must set the Network Type to “AD400 (wireless only)” on the Serial Channel (in SG software).
1.4.2 ADDING AD300’S TO AN EXISTING AD400 SYSTEM
a) DEDICATED NETWORK: You can install AD300 hardwired readers onto a separate DSI section. In this case
you must set the Network Type to “AD300 (hardwired only)” the Serial Channel (in SG software) for the new
AD300 network bus. Note: It is a requirement that even hardwired readers have a PIM address. Therefore the
SG software auto-assigns a PIM number to the Reader that matches the binary address of the AD300 Reader.
b) MIXED NETWORK: You can install the AD300 hardwired reader onto the same network bus with existing
AD400 wireless hardware as long as you do the following:
You must address the AD300 Readers to a binary value that is not used by any AD400 readers on the same
network bus.
You must use treat the binary address of an AD300 reader its own PIM number; and therefore you cannot
give the same binary address to an AD300 Reader and an AD400 PIM.
[Example: if an AD300 Reader is addressed to “4”, then there cannot be any AD400 PIMs addressed to 4].
You must set the Network Type to “AD300 & 400 (mixed-network)” on the Serial Channel (in SG software).
See other sections in this guide for diagrams of the mixed-networks and dedicated networks. Also
See Creating a “Mixed-Network” Channel and Creating an AD300-Only Channel for step-by-step
instructions.
System Galaxy Integration to Schlage AD400/AD300 Page 8

Table of Contents

Related product manuals