7.2.4
Life Load: Input States
Life Load . Assign_1_ Not in menu tree, only: Event recorder
Assignement 1 example_
7.2.5 Life Load: Signals (Output States)
Life Load . Active [Operation / Status Display / All Actives]
[Operation / Status Display / Life Load]
Signal: active
Life Load . Alarm [Operation / Status Display / Alarms]
[Operation / Status Display / Life Load]
Signal: Alarm
7.2.6
Life Load: Values
Life Load . < 0.4 In [Operation / Condition Monitoring / Life Load (Values)]
Number of operating days with measured current values within this range
Life Load . 0.4 ... 0.5 In
. . .
Life Load . 1.1 ... 1.2 In
[Operation / Condition Monitoring / Life Load (Values)]
Number of operating days with measured current values within this range
Life Load . > 1.2 In [Operation / Condition Monitoring / Life Load (Values)]
Number of operating days with measured current values within this range
Life Load . Time to Alarm [Operation / Condition Monitoring / Life Load (Values)]
Time (displayed in days) until an alarm signal is issued, because the device has been connected to too high
phase currents for a too long time. (The time counts backwards from the »Threshold t« setting to 0. The Direct
Command »Rst. Alarm« sets it back to »Threshold t«.)
33WIC1WIC1-2.0-EN-REF
7 Statistics
7.2.4 Life Load: Input States